IN STOCK
70,000 lbs/hr Trailer-Mounted
One (1) Low NOx Trailer-Mounted 70,000 lbs/hr packaged watertube boiler,
300 psi design pressure, set to burn natural gas or No. 2 oil, including
but not limited to the following scope of supply:
- Boiler Trim
- Siteglass
- Water column with high and low water alarms
- Continuous blowdown metering valve
- Water sample cooler
- Blowdown valves
- Feedwater stop check valves
- Low water cut-off
- Auxiliary low water cut-off
- Safety valves set @ 300 psi (shipped loose)
- Single element pneumatic feedwater regulator with three valve by-pass,
inlet strainer, and pressure/temperature indicators
- Low NOx burner (30 ppm NOx while firing natural gas with FGR)
- Forced draft fan with 75 hp TEFC motor and starter
- Burner Management System with first out annunciator
- Single point positioning combustion controls
- NEMA 4 and 12 electrical enclosures and sealtight conduit
- Fused electical disconnect with single power supply entrance connection
- Economizer piping mounted on unit
- Fuel oil pump for #2 fuel oil operation; mounted, piped and wired
- Eight inch non-return valve (shipped loose)
- FGR Duct (mounted)
- Stub stack (shipped loose)
- All equipment shall meet FM, IRI, NFPA and California Code Insurance
requirements
- Boiler is designed for outdoor installation and is weather protected
except for freezing conditions
- Connection Sizes:
- Steam: 8" 300 psi flange
- Oil: 1 1/2" screwed inlet 3/4" return
- Gas: 3" 150 psi flange
- Water: 2 1/2" 300 psi flange
- Blowdown: 1 1/2" 300 psi flange
- Atomizing air/steam: 1"/1 1/2" screwed
- Chemical feed: 1" screwed
- Instrumental Air: 3/8" NPT
- Dimensions (including trailer)
- Length: 50' 6"
- Width: 10" 8"
- Height: 14' 0"
- Shipping Weight: 85,000 pounds
- Operating Weight: 102,600 pounds
|